1 ~ 10V Dimming Output 12V Microwave Sensor Daylight Monitoring Function

Place of Origin Shenzhen, China
Brand Name Hynall
Certification RED, FCC, RoHS
Model Number HNS101D
Minimum Order Quantity 300pcs
Price To be negotiated
Packaging Details Bubble bag + carton. (color box or blister package also available on request)
Delivery Time 3~4 weeks for bulk orders
Payment Terms T/T
Supply Ability 50,000pcs / month

Contact me for free samples and coupons.

Whatsapp:0086 18588475571

Wechat: 0086 18588475571

Skype: sales10@aixton.com

If you have any concern, we provide 24-hour online help.

x
Product Details
Input Voltage 12V DC (5V & 24V Version Available On Request) Input Current ≥25mA
Control Type Tri-level Dimming Control Detection Range Max. 12m In Diameter
Mounting Height 3~6m Operation Temperature -20℃ ~ +70℃
High Light

12v motion sensor switch

,

outdoor motion sensor

,

12V Microwave Sensor Daylight Monitoring

Leave a Message
Product Description

              1 ~ 10V Dimming Output , 12V Microwave Sensor , Daylight Monitoring Function

 

12V DC input motion sensor with 1~10v dimming output and DIP switch setting, dual-processor technology to differentiate the natural light and lamp light, daylight monitoring function available.

 

1 ~ 10V Dimming Output 12V Microwave Sensor Daylight Monitoring Function 0

 

Features--

 

5.8GHz C-band microwave, tri-level dimming function.

Input voltage 12V DC (5V & 24V DC version available on request).

Input current:≥25mA.

1~10V dimming output.

Super compact, flexible to be integrated into any suitable fixtures.

Dual-processor technology, real Daylight monitoring function for built-in application.

8 pin DIP switch setting, multiple options to meet different customer demands.

Detection range up to 12m in diameter.

Mounting height: 3~6m.

Operation temperature; -20℃ ~ + 70℃.

RoHS compliant.

 

Settings--

 

Detection range

Detection range can be reduced by selecting the combination

on the DIP switches to fit precisely each application.

1 ~ 10V Dimming Output 12V Microwave Sensor Daylight Monitoring Function 1

 

Hold-time

Hold-time means the time period to keep the lamp on 100% after motion detected.

*when hold-time set as 3s, sensor enters into test mode, this test mode is mainly for users to      choose the desired detection range. In this mode, the daylight sensor is disabled, when there is no motion, fixture keeps off, when there is motion detected, fixture keeps a cycle of 3s on and 2s off.

1 ~ 10V Dimming Output 12V Microwave Sensor Daylight Monitoring Function 2

 

Daylight sensor

          Daylight sensor means the daylight threshold to enable or disable the sensor function.

"Disable":        The sensor works always, even during daylight.

"50lux":            The sensor works only in twilight.

                  "10lux, 2lux":  The sensor works only in the dark.

1 ~ 10V Dimming Output 12V Microwave Sensor Daylight Monitoring Function 3

 

Stand-by period

This is the time period that the lamp remains at a low light level before it is completely switched off in the long absence of people.

    “+∞”: means bi-level dimming control, the fixture never switch off.

1 ~ 10V Dimming Output 12V Microwave Sensor Daylight Monitoring Function 4

 

Stand-by dimming level

This is the dimmed low light level you would like to have after the hold-time in the absence of people.

1 ~ 10V Dimming Output 12V Microwave Sensor Daylight Monitoring Function 5

 

Detection pattern--

 

1 ~ 10V Dimming Output 12V Microwave Sensor Daylight Monitoring Function 6

 

Daylight monitoring function--

 

Utilizing the Dual-processor technology, this sensor can tell the difference of natural light and artificial light(lamp) from behind the diffuser, switch on automatically(even without movements) when the ambient light is below target value, and then switch off automatically whenever the artificial light is not required(ambient light is bright enough).

 

This is the REAL & INTELLIGENT daylight monitoring sensor for built-in installation.

 

Note: Lux-Off sampling time—30s; Lux-On sampling time—10s.

  Lux-On function takes effect only when standby dimming period set at+∞.

1 ~ 10V Dimming Output 12V Microwave Sensor Daylight Monitoring Function 7